首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Condensation and pressure drop characteristics of R600a in a helical tube-in-tube heat exchanger at different inclination angles
【24h】

Condensation and pressure drop characteristics of R600a in a helical tube-in-tube heat exchanger at different inclination angles

机译:螺旋管式换热器中R600a在不同倾角下的冷凝和压降特性

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

An experimental investigation is carried out to study the condensation and pressure drop characteristics of R-600a inside a helical tube-in-tube heat exchanger. The axis of the helical condenser was located at inclination angles of zero, +30 degrees, +60 degrees and +90 degrees from horizontal. The test condenser was a counter flow helical tube-in-tube heat exchanger. The diameter, pitch, height and the number of coil turns were 305 mm, 35 mm, 210 mm and 6, respectively. Experiments were also implemented in a straight tube-in-tube condenser; all tests were performed at average saturation temperatures ranging between 38.5 and 47 degrees C. Refrigerant mass fluxes varied in the range of 155-265.5 kg m(-2) S. The average vapor quality varied between 0.11 and 0.78. The effects of inclination angle, mass flux and average vapor quality on the heat transfer coefficient and pressure drop are discussed. It is shown that the highest and lowest values of the heat transfer coefficient occur for 30 degrees and 90 degrees inclination angles respectively, while the pressure drop has the maximum value for the horizontal case. Compared to the horizontal straight condenser, the average heat transfer coefficient and the pressure drop of the horizontal helical condenser increase in the range of 24-165% and 33-157%, respectively. Moreover, the performance index values of horizontal helical condenser are about 15-41% higher than that of inclination angle of 90 degrees. (C) 2015 Elsevier Ltd. All rights reserved.
机译:进行了实验研究以研究R-600a在螺旋管式换热器内部的冷凝和压降特性。螺旋冷凝器的轴线相对于水平面的倾斜角度为零,+ 30度,+ 60度和+90度。测试冷凝器是逆流螺旋管内换热器。直径,节距,高度和线圈匝数分别为305 mm,35 mm,210 mm和6。实验也在直管式冷凝器中进行;所有测试均在38.5至47摄氏度的平均饱和温度下进行。制冷剂的质量通量在155-265.5 kg m(-2)S的范围内变化。平均蒸汽质量在0.11至0.78之间变化。讨论了倾角,质量通量和平均蒸汽质量对传热系数和压降的影响。结果表明,传热系数的最大值和最小值分别出现在30度和90度倾斜角上,而压降在水平情况下具有最大值。与卧式直式冷凝器相比,卧式螺旋式冷凝器的平均传热系数和压降分别在24-165%和33-157%的范围内增加。此外,水平螺旋冷凝器的性能指标值比90度倾斜角大约高15-41%。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号