Experimental evaluation of the thermal performance at different environmental conditions of a low temperature display case with built-in compressor and water-cooled condenser

机译:用内置压缩机和水冷式冷凝器的低温展示箱不同环境条件热性能的实验评价

获取原文
获取原文并翻译 | 示例
           

摘要

This paper reports the results of experimental tests performed according to ISO 23953 in a vertical closed low temperature display case to evaluate the influence of the environment where it is installed (climatic class) in the energy consumption and thermal performance. The compressor and the condenser are attached to the display case and an external water circuit is used to provide air-chilled water to the condenser. The need for this type of equipment arises from the numerous small stores without air conditioning system and without space for placing a remote cooling rack. Keeping the external environment temperature constant and consequently the refrigerant condensing temperature, changing climatic class n.degrees 3 (T-a = 25 degrees C and phi(a) = 60%) to n.degrees 6 (T-a = 27 degrees C and phi(a) = 70%), the compressor energy consumption increases 8% to 10% and the highest temperature of the warmest product simulator increases + 3.0 degrees C. At the same climatic class, the water temperature increases with the external environment temperature. The compressor energy consumption increases 13% and 8% when the refrigerant condensing temperature increases from 40 degrees C to 45 degrees C and from 45 degrees C to 50 degrees C, respectively. Thus, refrigeration equipment with compressor and condenser attached is susceptible to the climatic variation of the internal and external environment. In applications with large climatic amplitude, the components must be designed to meet all the operating situations.
机译:本文报告了根据ISO 23953在垂直封闭的低温展示案件中进行的实验测试的结果,以评估能量消耗和热性能中安装(气候类)的环境的影响。压缩机和冷凝器附接到显示壳体,外部水电路用于向冷凝器提供空气冷却的水。对于这种类型的设备的需求来自许多小型商店,没有空调系统,并且没有空间放置遥控架。保持外部环境温度恒定,因此制冷剂冷凝温度,变化的气候级别3(Ta = 25摄氏度和Phi(a)= 60%)至N.degrees 6(Ta = 27摄氏度和Phi(a )= 70%),压缩机能量消耗增加了8%至10%,最热产品模拟器的最高温度增加+ 3.0摄氏度。在相同的气候类中,水温随着外部环境温度而增加。当制冷剂冷凝温度从40℃至45℃且45℃至50度C增加时,压缩机能量消耗增加了13%和8%。因此,具有压缩机和冷凝器的制冷设备容易受到内部和外部环境的气候变化。在具有大气候幅度的应用中,必须设计部件以满足所有操作情况。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号