首页> 外文期刊>材料と環境 >Effect of Residual Carbon Deposits on Corrosion Behavior of Copper Tube Filled with Water
【24h】

Effect of Residual Carbon Deposits on Corrosion Behavior of Copper Tube Filled with Water

机译:残留碳沉积物对用水充满铜管腐蚀行为的影响

获取原文
获取原文并翻译 | 示例
           

摘要

Effects of residual carbon deposits and water quality on corrosion behavior of copper tubes for air conditioning systems have been investigated by field tests and electrochemical measurements. Copper tubes with/without residual carbon deposits were filled with tap or circulated water in storage tank for 60 days. Patina and slight corrosion attack only occurred on the surface of copper tube, which has the residual carbon film and is filled with the circulated water. The corrosion potential of the copper tube with high carbon deposits was higher than that with low carbon deposits. The galvanic current density from copper tube with high carbon deposits to copper tube with low carbon deposits shows a gradual increase. This means that the high residual carbon area of surface could be the cathodic area when the corrosion occurs. It is found that the combinations of residual carbon deposits and contaminated water are detrimental to the corrosion of copper tube.
机译:野外试验和电化学测量研究了残留碳沉积物对空调系统铜管腐蚀行为的影响。 带/不含残留碳沉积物的铜管填充储罐中的龙头或循环水60天。 Patina和轻微的腐蚀攻击仅发生在铜管表面上,该铜管表面具有残留的碳膜,填充有循环的水。 具有高碳沉积物的铜管的腐蚀电位高于低碳沉积物。 具有高碳沉积到具有低碳沉积物的高碳沉积物的铜管电流密度显示出逐渐增加。 这意味着当腐蚀发生时,表面的高残留碳面积可以是阴极区域。 发现残留碳沉积物和受污染的水的组合对铜管的腐蚀有害。