Experimental performance assessment of a hermetic reciprocating compressor operating in a household refrigerator under on-off cycling conditions

机译:在开关循环条件下在家用冰箱中操作的密封往复式压缩机的实验性能评估

获取原文
获取原文并翻译 | 示例
           

摘要

This paper reports a study on the performance of a hermetic reciprocating compressor operating in a household refrigerator. The refrigerator was provided with sensors to measure the mass flow rate and evaporating and condensing pressures, while the compressor was instrumented with thermocouples in selected components and pressure transducers to measure the p-V diagram. Tests were conducted at ambient temperatures of 32 degrees C, 25 degrees C and 16 degrees C with different freezer cut-offtemperatures (-10 degrees C, -16 degrees C and -19 degrees C). The phenomena that affect the mass flow rate and power consumption were evaluated during typical on-periods. It was observed that the thermodynamic efficiency of the compressor varied by 5-10% during the first few minutes after the compressor start-up, but remained virtually constant throughout the remainder of the on-period. The results showed that the volumetric and thermodynamic efficiencies tend to increase at lower ambient temperatures, while the overall efficiency of the compressor remains practically constant. Additionally, the compressor average temperatures and efficiencies collected from the application tests were compared to data obtained with calorimeters, revealing that the two sets of data do not differ much from each other. (C) 2018 Elsevier Ltd and IIR. All rights reserved.
机译:本文报告了在家用冰箱中操作的密封往复式压缩机的性能研究。冰箱设有传感器以测量质量流量和蒸发和冷凝压力,而压缩机用选定的部件和压力传感器的热电偶仪表,以测量P-V图。在32℃,25℃和16摄氏度的环境温度下进行测试,用不同的冷冻室切割 - 化妆品(-10℃,-16摄氏度和-19℃)。在典型的在内的时间内评估影响质量流量和功耗的现象。观察到压缩机的热力学效率在压缩机启动后的最初几分钟内变化了5-10%,但在接通期的剩余时间内保持几乎恒定。结果表明,在环境温度下,体积和热力学效率趋于增加,而压缩机的整体效率仍然恒定。此外,将从施用测试收集的压缩机平均温度和效率与热量计获得的数据进行比较,揭示两组数据彼此不差异。 (c)2018年Elsevier Ltd和IIR。版权所有。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号