首页> 外文期刊>Analysis and applications >Performance Analysis of Active Energy Meters Under Non-Sinusoidal Conditions
【24h】

Performance Analysis of Active Energy Meters Under Non-Sinusoidal Conditions

机译:非正弦状况下有效能量计的性能分析

获取原文
获取原文并翻译 | 示例
           

摘要

The performance of electrical energy meters in non-sinusoidal conditions has been discussed since the early 20th Century and as of yet has not reached a fully comprehensive standardization. Within this context, this paper aims to update the present understanding on the subject through a closer look at the power definitions established by the IEEE Std. 1459-2010. The paper concentrates its goals across two different approaches. The first deals with the analytical development in the time domain, aiming at the decomposition of the instantaneous power in its different elementary components. The second, in turn, deals with the development of several calibration tests in different active electrical energy meters considering different voltage and current waveforms. The results show that the measurement deviations in non-sinusoidal conditions may be greater than 30% in some practical cases, which reinforces the need for more specific standards concerning the subject.
机译:自20世纪初以来,已经讨论了非正弦状况中电能表的性能,尚未达到全面的全面标准化。 在此背景下,本文旨在通过仔细研究IEEE STD建立的功率定义来更新对主题的本理解。 1459-2010。 本文集中了两种不同方法的目标。 第一批关于时域的分析发展,旨在瞄准其不同基本组分中瞬时功率的分解。 第二轮,又处理了考虑不同电压和电流波形的不同主动电能表中几种校准测试的开发。 结果表明,在一些实际情况下,非正弦状况中的测量偏差可能大于30%,这加强了对受试者更具体的标准的需求。