The present paper reports the development of the refrigeration system that is applied to 70 MW class superconducting generators. The main subject in developing the refrigeration system for verification tests on site was to develop technology for removing impurities in helium gas, which largely affects its reliability, and to further improve the reliability and efficiency of its man components as screw compressors, turbo expanders, and a low temperature adsorber. Thus this paper deals with its planning and performance testing as well as automatic control in different modes of operation (such as cool-down, steady-state and heat run) and also the reliability analysis. It was verified that the developed refrigeration system demonstrated a higher reliability of 14,637 h mean time between failure, larger than 10,000 h. The total operation time at steady state has reached 9320 h with no failures in the entire testing period.
机译:本文报道了应用于70 MW级超导发电机的制冷系统的发展。开发用于现场验证测试的制冷系统的主要主题是开发用于去除氦气中杂质的技术,该技术会大大影响氦气的可靠性,并进一步提高其作为螺杆压缩机,涡轮膨胀机和涡轮增压器的手动部件的可靠性和效率。低温吸附器。因此,本文涉及其计划和性能测试以及在不同运行模式(如冷却,稳态和热运行)下的自动控制以及可靠性分析。经验证,所开发的制冷系统具有更高的可靠性,平均故障间隔时间为14637小时,大于10000小时。稳定状态下的总运行时间达到了9320 h,在整个测试期间内没有任何故障。