The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer with fault current limiting function

机译:具有故障限流功能的6.9 kV / 2.3 kV 400 kVA级YBCO型变压器的短路测试结果

获取原文
获取原文并翻译 | 示例
       

摘要

We are developing an elemental technology for 66/6.9 kV 20 MVA-class superconducting power transformer with fault current limiting function. In order to obtain the characteristics of YBCO conductor when the AC over current supplied to the conductor, the model coils were manufactured with YBCO tapes and tested. Based on these results, we manufactured the 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer with fault current limiting function and performed short-circuit test. At the 0.25 s after short-circuit, the short-circuit current of primary winding was limited to about 174 A for a prospective current of 559 A. It was consistent with the design. The I-V characteristics of the winding did not change before and after the test. We consider the model transformer to be able to withstand AC over-current with the function of current limiting. The results suggest the possibility to design YBCO superconducting transformers with fault current limiting function for practical power grid.
机译:我们正在开发具有故障电流限制功能的66 / 6.9 kV 20 MVA级超导电力变压器的基本技术。为了在向导体提供交流过电流时获得YBCO导体的特性,使用YBCO胶带制造了模型线圈并进行了测试。根据这些结果,我们制造了具有故障限流功能的6.9 kV / 2.3 kV 400 kVA级YBCO模型变压器,并进行了短路测试。在短路后0.25 s时,对于559 A的预期电流,初级绕组的短路电流限制在174 A左右。这与设计相符。在测试前后,绕组的I-V特性没有变化。我们认为该模型变压器能够承受具有电流限制功能的交流过电流。结果表明为实际电网设计具有故障限流功能的YBCO超导变压器的可能性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号