首页> 外文期刊>Электричество >Diagnosing insulation of electrical machine windings by means of constant voltage
【24h】

Diagnosing insulation of electrical machine windings by means of constant voltage

机译:通过恒定电压诊断电机绕组的绝缘

获取原文
获取原文并翻译 | 示例
           

摘要

An equivalent circuit for insulation of electrical machines with thermally and electrically warm insulation is proposed. It can be used for developing methods of insulation tests and estimating the insulation technical condition. The diagnosticsmethod proposed is based on the following tests under constant voltage. 1. Obtaining the winding insulation leakage current time diagram when switching-on U{sub}nom. 2. Measuring steady-state leakage current when voltage rising from 0 to 2U{sub}nom anddetermining the characteristic of equivalent insulation resistance R{sub}e =f(U). 3. Charging insulation system up to voltage U{sub}nom then shortcircuiting with duration t{sub}s (t{sub}s depending on the insulation rated voltage and the degree of wearand tire of insulation, t{sub}s= 1-60s); determining the voltage recover' curve U{sub}r (t) after opening the chunt circuit. On the basis of results of the tests mention above it is possible to determine criteria for estimating the technical conditionalof insulation.
机译:提出了用于具有热绝缘和电绝缘的电机绝缘的等效电路。可用于开发绝缘测试方法和评估绝缘技术条件。提出的诊断方法基于在恒定电压下的以下测试。 1.接通U {sub} nom时,获得绕组绝缘泄漏电流时间图。 2.测量电压从0上升到2U {nom}时的稳态漏电流,并确定等效绝缘电阻R {sub} e = f(U)的特性。 3.对绝缘系统进行充电,直至电压U {sub} nom,然后在持续时间t {sub} s(t {sub} s,具体取决于绝缘额定电压以及绝缘的磨损程度和轮胎的疲劳程度,t {sub} s = 1 -60秒);确定在打开分流电路后的电压恢复曲线U {sub} r(t)。根据上述测试结果,可以确定评估绝缘技术条件的标准。