首页> 外文期刊>大气环境学会志 >機械通風式冷却塔からの白煙予測手法(その3)
【24h】

機械通風式冷却塔からの白煙予測手法(その3)

机译:机械通风冷却塔的白烟预测方法(第3部分)

获取原文
获取原文并翻译 | 示例
           

摘要

A new visible plume model is developed to predict visible plume, temperatulで ,moisture and droplet from a mechanical-draft cooling tower. Thedeveloped model is a normal Gaussian plume model for moistme andtemperature,consideringfan configurationwet-drycombined coolingtower system,verticalatmospherictemperaature andatmospheric stability.Theaccuracyofpreviousmodels(FOG,SACTI) andthe developed model is investigated to compare the model results with observation conducted in Japan. The results show that the previous models can not accurately predict the visible plume length and height because they have mainly developed for a natural -drift cooling tower, which is different type from a mechanical -draftcooligtower.On the other hand,thevisible plume length and height predicted by the developed model are in good agreementwith the observation,andstatistical data analysis also shows tlatthe model provides better performance than the previous models. Furthermore,the model predicts not onlyttheevisible plumeregion but alsotemperature,moistureanddroplet from the coolulg tower.
机译:开发了一种新的可见羽流模型,以预测机械通风冷却塔中的可见羽流,温度,湿度和液滴。该模型是针对湿度和温度的正常高斯羽流模型,考虑了风扇配置的干湿组合冷却塔系统,垂直大气温度和大气稳定性。研究了先前模型(FOG,SACTI)的准确性,并将该模型与日本的观测结果进行了比较。结果表明,以前的模型无法准确预测可见羽流的长度和高度,因为它们主要是针对自然漂移的冷却塔开发的,与机械式冷却塔不同,另一方面,可见羽流的长度和高度也有所不同。所开发模型的预测结果与观测值吻合良好,统计数据分析也表明该模型提供了比以前的模型更好的性能。此外,该模型不仅可以预测可见的羽流区域,还可以预测冷却塔的温度,湿度和液滴。