Sprinkler heads are a mature product that can fail to function via a variety of different mechanisms. Mechanical damage and corrosion can occur year round. Additionally, there can be seasonal failures due to creep of fusible alloys in summer. Serious problems also have occurred due to sticking of sliding O-ring seals. These problems have lead to product recalls, and subsequent revisions in design standards.
机译:喷头是一种成熟的产品,可能无法通过多种不同的机制发挥作用。机械损坏和腐蚀可能会全年发生。另外,由于夏季易熔合金的蠕变,可能会出现季节性故障。由于滑动O形圈密封件的粘连,也出现了严重的问题。这些问题导致了产品召回和设计标准的后续修订。