首页> 外文期刊>Journal of Failure Analysis and Prevention >Analysis on the Fire Accident of Hydrocracking Unit
【24h】

Analysis on the Fire Accident of Hydrocracking Unit

机译:加氢裂化装置火灾事故分析

获取原文
获取原文并翻译 | 示例
           

摘要

A fire accident occurred in an oil refinery in north China. The on-site investigations proved that the fire was triggered by the leakage of tail oil from one hole on the pipeline. The detailed analysis of the metallurgical microstructure of related pipelines indicated that some micro-cracks existed in the pipeline. Under the action of tensile stress induced by inner pressure, one of the micro-cracks kept propagating and evolved into macro-crack; under the action of cyclic circumferential tensile stress and stress concentration in the crack tip, the macro-crack was transformed to penetrated crack, finally the crack was torn open by inner pressure, and then the leakage hole on the pipeline was formed and fire accident occurred.
机译:中国北方某炼油厂发生火灾。现场调查证明,起火是由管道上一个孔的尾油泄漏引起的。对相关管道的冶金组织进行详细分析,发现管道中存在一些微裂纹。在内部压力引起的拉应力的作用下,其中一个微裂纹不断扩展并发展为大裂纹。在裂纹尖端周期性的周向拉伸应力和应力集中作用下,宏观裂纹转变为渗透裂纹,最终裂纹被内压撕开,形成管道上的泄漏孔,发生火灾事故。 。