A 2 in. schedule 40 steel (60.3 mm diameter, 3.91 mm wall) core pipe in an evaporator overheads discharge line broke at several locations downstream from a section of the line that bridges a road. The failure occurred during pump restart. Fish mouth openings that developed along the pipe seams were initiated at lack of fusion defects in the pipe welds. Full drainage of the water from the pipe did not occur when the pump was shut down because such drainage created an upstream vacuum in the piping system. Freezing of water in the pipe (the line was not heat traced) and water hammer during pump restart each contributed to the extensive deformation and tearing observed at the breaks. The weld flaws served as crack initiation sites and the water hammer provided the overpressure that led to the fish mouth fracture. The pipe was replaced and a vacuum break was installed to eliminate the drainage problem.
机译:蒸发器顶部排放管线中的2英寸40号钢管(直径60.3 mm,壁厚3.91 mm)芯管在桥接道路的管线段的下游几个位置处断裂。泵重启期间发生故障。沿管缝形成的鱼嘴开口是在管焊缝中没有融合缺陷的情况下引发的。关闭泵时,管道中的水没有完全排出,因为这种排出会在管道系统中产生上游真空。管道中的水冻结(没有追踪热线),并且在泵重新启动期间发生水锤现象,均导致在断裂处观察到广泛的变形和撕裂。焊缝缺陷是裂纹的起始点,水锤提供的超压导致鱼嘴破裂。更换了管道,并安装了真空断路器以消除排水问题。