A theroretical and experimental investigation is carried out on the dynamic behavior of a dehumidification system used to dry out the wet floor in a beverage factory.The dehumidification system consists of an absorption-type rotary dehumidifier with lithium chloride salt coated on the honeycomb monolith.Experimental runs were carried out in the factory.By coupling a previous dynamic model of the dehumidifier with an evaporation model of the wet concrete floor,good agreement has been obtained between the simulated and experimental results,thus confirming the applicability of the integrated model.To obtain better performance of the integrated dehumidification system,the model is next used to investigate the effects of varous system inputs and paameters on its dynamic preformance.The results show that the paired velocities of dehmidified and regeneration outlet airs,and the pre-heating temperature of the regeneration air have more prominent effect on dehumidification efficiency than the other factors.It is possible to both reduce the room relative humidity below 50% and dry out the water on the floor within 12 hours of dehumidificaion.The most suitable dehumidification conditions among those investigated are:velocity of room air 0.06 m/s,inlet temperature of regenerated hot air 343 K,velocity of regenerated hot air 05 m/s,air velocity in dehumidifying section 0.68 m/s and rotational speed of honeycomb 10 rph.
机译:对用于干燥饮料厂湿地板的除湿系统的动力特性进行了理论和实验研究,该除湿系统由吸收式旋转除湿机组成,该吸湿式旋转除湿机的蜂窝状整体上涂有氯化锂盐。通过将除湿机的先前动态模型与湿混凝土楼板的蒸发模型相结合,在模拟和实验结果之间取得了良好的一致性,从而证实了集成模型的适用性。集成除湿系统的性能更好,接下来将使用该模型研究各种系统输入和参数对其动态性能的影响。结果表明,除湿和再生出口空气的成对速度,以及除湿器的预热温度再生空气对除湿效率的影响比这些因素是可能的,既可以将房间的相对湿度降低到50%以下,又可以在除湿的12小时内使地板上的水变干。研究中最合适的除湿条件是:室内空气的速度0.06 m / s,进风口再生热风温度343 K,再生热风速度05 m / s,除湿段风速0.68 m / s,蜂窝转速10 rph。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号