Seventy to eighty percent of industrial water is cooling water,and cooling systems let off much wastewater every day.It is worthful to treat and reuse the wastewater from cooling towers.A study was undertaken to evaluate the efficiency of the combined processes,known as integrated membrane systems(IMS),for the treatment of wastewater from cooling towers.Two IMS employed were sand filtration-MF-RO and sand filtration-UF-RO.MF and UF membranes were found to be effective to reduce turbidity and the silt density index of the wastewater.Both of them could provide eligible feed for sequent RO membranes.The product water of the both IMS could fulfill reuse requirements.
机译:百分之七十至八十的工业用水是冷却水,冷却系统每天排放大量废水。处理和再利用冷却塔中的废水非常有价值。进行了一项研究,以评估组合过程的效率,这称为集成膜系统(IMS),用于处理冷却塔废水。采用两种IMS:沙滤-MF-RO和沙滤-UF-RO。发现MF和UF膜可有效降低浊度和淤泥密度指数两者均可为后续的反渗透膜提供合格的进料,两个IMS的产水均可满足回用要求。