This paper presents the results of a research project aiming the diagnostic of the silicon carbide surge arresters. These surge arresters are being gradually replaced by the gapless zinc oxide ones, therefore, it is very important to select the surge arresters that are more degraded in order to avoid failures in the field. Tests were performed at the laboratory and the results showed a good correlation between the leakage current measurement, radio-influence voltage test and thermovision and the presence of deterioration in the internal parts of the surge arresters. The results obtained in this research might help the utility to develop more adequate maintenance programs and to select the silicon carbide surge arresters that need replacement.
机译:本文介绍了旨在诊断碳化硅电涌放电器的研究项目的结果。这些电涌放电器正逐渐被无间隙的氧化锌所取代,因此,选择性能更高的电涌放电器以免在现场发生故障非常重要。在实验室进行了测试,结果表明泄漏电流测量,无线电影响电压测试和热敏成像以及电涌放电器内部部件的劣化之间存在良好的相关性。这项研究中获得的结果可能有助于公用事业公司制定更充分的维护计划,并选择需要更换的碳化硅电涌放电器。