This paper proposes a new correlation factor based islanding detection method for use of grid-connected distributed synchronous generator. The proposed correlation factor method is based on voltage fluctuation injection, which can be obtained through regulating the field current of the distributed synchronous generator periodically. The correlation factor between the periodic regulating signal and the perturbed voltage is then used as an islanding detection index. When distributed synchronous generator is grid-interconnected, the correlation factor is lower than a threshold value. In contrast, as an islanding occurs, the correlation factor would become much higher than the threshold value. In this paper, experiments are conducted to illustrate the principles of the proposed technique. The test results show that the new proposed method is reliable, economical, and easy for implementation for islanding detection of distributed synchronous generator.
机译:提出了一种新的基于相关因子的孤岛检测方法,用于并网分布式同步发电机。提出的相关因子方法基于电压波动注入,可以通过定期调节分布式同步发电机的励磁电流来获得。然后将周期性调节信号和干扰电压之间的相关因子用作孤岛检测指标。当分布式同步发电机并网时,相关因子低于阈值。相反,当发生孤岛时,相关因子将变得远高于阈值。在本文中,进行了实验以说明所提出技术的原理。测试结果表明,该方法可靠,经济,易于实现,用于分布式同步发电机的孤岛检测。