This paper deals with diagnostic methods of the internal faults in power transformers. The diagnostic process uses some of the current diagnosis methods (e.g. oil test, dissolved gases analysis (DGA), partial discharge (PD), etc.) to determine the condition of the transformer. In this process, the most frequent diagnostic methods were listed and applied practically to be compared. A conventional faulty oil-immersed transformer 400 V/10 kV, 100 kVA was diagnosed and tested with different methods. The parameters and results were compared with a normal working transformer with the same parameters and age. After that an opening of the transformer was performed to approve and to make a visual verification of the diagnostic methods and the used devices. Among the applied methods, the frequency response analysis FRA reflects the real situation of the internal faults such as short circuits, mechanical displacement and deformation of the transformer windings.
机译:本文探讨了电力变压器内部故障的诊断方法。诊断过程使用一些当前的诊断方法(例如,油测试,溶解气体分析(DGA),局部放电(PD)等)来确定变压器的状态。在此过程中,列出了最常见的诊断方法,并在实际中进行了比较。常规故障油浸式变压器400 V / 10 kV,100 kVA可以通过不同方法进行诊断和测试。将参数和结果与具有相同参数和使用年限的正常工作变压器进行比较。此后,打开变压器以批准并视觉诊断诊断方法和使用的设备。在应用的方法中,频率响应分析FRA反映了内部故障的真实情况,例如短路,机械位移和变压器绕组的变形。