Information about moisture content contained within oil-paper insulated cable can be found at high frequencies where the minimum of the response occurs. Increase in moisture content not only affects the value of tan delta_(min) but also the frequency at which this minimum value occur. Apart from moisture, temperature is another factor that affects the frequency at with tan delta_(min) value occurs. Interestingly, magnitude of tan delta_(min) remains stable with temperature. Using some part of previous work, an expression that relates moisture content and time is derived. Further work is required on the practical applicability of this formula. Only cable that has been seriously affected by moisture cable can be detected by measuring tan delta at low frequencies.
机译:关于油纸绝缘电缆中包含的水分含量的信息可以在响应最小的高频处找到。水分含量的增加不仅会影响tan delta_(min)的值,还会影响出现该最小值的频率。除水分外,温度是另一个影响频率的因素,当tan del __(min)值出现时。有趣的是,tanδ_(min)的大小随温度保持稳定。使用先前工作的某些部分,可以得出与水分含量和时间有关的表达式。该公式的实际适用性还需要进一步的研究。通过在低频下测量损耗角正切,才能检测出受潮电缆严重影响的电缆。