We present and analyse the collective statistical results of a long-term field study quantifying the number of lightning strikes to buildings equipped with lightning protection systems. The observations were made over the period 1990-2003 in a region with one of the highest lightning activities in the world. The data sample comprised 86 structures with a mean height and exposure time of 57 metres and 6.9 yr, respectively. These structures were subjected to 384 flashes over the total observation time of 592 yr. The positioning of the protective air terminals on these structures was carried out with an improved electrogeometric model of lightning attachment.
机译:我们提出并分析了一项长期的现场研究的集体统计结果,该研究量化了配备防雷系统的建筑物的雷击数量。这些观测是在1990年至2003年期间,在一个闪电活动最高的地区进行的。数据样本包括86个结构,平均高度分别为57米和6.9年。这些结构在592年的总观测时间内经受了384次闪蒸。保护性空气终端在这些结构上的定位是通过改进的雷电电几何模型完成的。