首页> 外文期刊>日本建築学会環境系論文集 >模型実験によるソーラーチムニーとチムニーシャフトの接続状態による自然換気性能の検討
【24h】

模型実験によるソーラーチムニーとチムニーシャフトの接続状態による自然換気性能の検討

机译:通过模型实验,通过太阳能烟囱和烟囱井筒的连接状态检查自然通风性能

获取原文
获取原文并翻译 | 示例
       

摘要

This study examined the ventilation performance of solar chimney by the relations of the inlet and outlet, the solar radiation heat-receiving chimney area, the connection conditions of the chimney shaft and chimney. As a result, the ventilation rate was increased in order of 16 m~2, 4 m~2, 8m~2 chimney horizontal cross sections. And when the section area was same, the increase of the solar radiation heat-receiving chimney area was effective than chimney height. A chimney shaft was narrower than a chimney was effective in the case of 16 a chimney cross section area. However, a chimney shaft was wider than a chimney was effective in the case of 4 m~2 a chimney horizontal cross section area. And the ventilation rate was not increased that much when the section area rate of the outlet for the inlet were more than 2.%自然換気に有効なソーラーチムニーとチムニーシャフトの接続状態について模型実験により検討した結果、以下の知見を得た。 1)チムニーの日射受熱面積が同じ(受熱面1面:北面)である場合、チムニー排気量はチムニー水平断面積が16 m~2 (形状Ⅱ)、 4m~2 (形状Ⅲ)、 8 m~2 (形状Ⅰ)の順位に多くなる結果であった。これはチムニー断面積が16 m~2のように大きい場合、チムニー内部表面とチムニー内部空気との熱伝達と形状抵抗が同時に小さくなるが、逆に4 m~2とチムニー断面積が小さい場合は両方大きくなるためと思われる。
机译:本研究通过进风口与出风口的关系,太阳辐射吸热烟囱的面积,烟囱井筒与烟囱的连接条件等方面,研究了太阳能烟囱的通风性能。结果,通风速率按16 m〜2、4 m〜2、8m〜2烟囱水平截面的顺序增加。并且当截面积相同时,太阳辐射接收烟囱面积的增加比烟囱高度有效。在烟囱横截面积为16的情况下,烟囱的宽度比烟囱的宽度窄。但是,在烟囱水平横截面积为4 m〜2的情况下,烟囱杆比烟囱更宽。当进气口的出气口截面积率大于2%时,通风率没有增加太多。自然换気に有效なソーラーチムーチムーーニーチムーーフトの接続状态について模型実験により検讨実験により検结果,以下の知见1)チムニーの日射受热面积が同じ(受热面1面:北面)である场合,チムニー排気量はチムニー水平断面积が16 m〜2(形状Ⅱ),4m〜2(形状Ⅲ) ,8 m〜2(形状Ⅰ)の顺位に多くなる结果であった。これはチムニー断面积が16 m〜2のように大きい场合,チムニー内部表面とチムニー内部空気との热伝达と形状抵抗が同时に小さくなるが,逆に4 m〜2とチムニー断面积が小さい场合は両方大きくなるためと思われる。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号