Electrostatic induction by power lines in parallel telephone lines and at crossings

机译:电力线在平行电话线和交叉口中的静电感应

获取原文
获取原文并翻译 | 示例
       

摘要

It is well known that the actual measurements of coefficients characterizing the electrostatic induction from power lines to parallel or transverse telephone lines do not always agree with the values obtained using the generally accepted theory. The paper analyses the possible causes of the observed discrepancies. By taking into account the effect of harmonics existing in the power system, the conclusion is reached that these discrepancies arise mainly through ignoring the effects of pylons or other earthed structures and the unevenness of the ground. The second part of the paper examines the relations between the values given by the simplified formulae contained in the Directives of the C.C.I.F. and those given by the more rigorous formulae. It is found that the C.C.I.F. formulae are generally adequate.
机译:众所周知,表征从电源线到平行或横向电话线的静电感应的系数的实际测量值并不总是与使用普遍接受的理论获得的值一致。本文分析了观察到的差异的可能原因。考虑到电力系统中存在的谐波影响,得出的结论是,这些差异主要是由于忽略了塔架或其他接地结构的影响以及地面的不平整而引起的。本文的第二部分研究了C.C.I.F.指令中包含的简化公式给出的值之间的关系。以及更严格的公式给出的那些。发现C.C.I.F.公式通常是足够的。