ADAPTIVE CURRENT PROTECTION AGAINST EARTH FAULTS IN 6 - 10 kV CABLE NETWORKS

机译:6-10 kV电缆网络中的接地故障自适应电流保护。

获取原文
获取原文并翻译 | 示例
           

摘要

In 6 - 10 kV cable networks with isolated neutral, overcurrent protections are widely applied to earth fault protection based on components of working frequency, and in compensated cable networks based on higher harmonics of the zero-sequence current. The selectivity and stability of functioning of the former is, to a significant extent, limited by the effect on their operation of transient processes during arc earth faults, and of the latter by the instability of the level of the higher harmonics in the SPEF current, depending on the network operating mode. An adaptive method is examined for implementing the specified protections to ensure improvement of their technical capability. 6 - 10 kV cable networks; single-phase earth faults; earth fault overcurrent protection; adaptive overcurrent protection.
机译:在具有中性线隔离的6-10 kV电缆网络中,过电流保护被广泛应用于基于工作频率分量的接地故障保护,以及基于零序电流的高次谐波的补偿电缆网络。前者功能的选择性和稳定性在很大程度上受到电弧接地故障对其瞬变过程操作的影响,而后者则受到SPEF电流中高次谐波电平的不稳定性的限制,取决于网络操作模式。为实施指定的保护措施以确保提高其技术能力,研究了一种自适应方法。 6-10 kV电缆网络;单相接地故障;接地故障过电流保护;自适应过电流保护。