Post-arc current measurements were made on a high-voltage SF/sub 6/ circuit breaker. A pyrotechnic device was used to protect the measurement shunt. The tests, performed at high current values between 40 and 63 kA, gave post-arc current levels of 0.5 to 2 A. Interpretation of the experimental results by the generalized Mayr model led to the determination of a set of parameters characteristic of the apparatus tested, thereby making it possible to find the test results and, in particular, to forecast cases of thermal failure.
机译:弧后电流测量是在高压SF / sub 6 /断路器上进行的。使用烟火装置保护测量分流器。在40至63 kA之间的高电流值下进行的测试给出了0.5至2 A的电弧后电流水平。广义Mayr模型对实验结果的解释导致确定了所测试设备的一组参数特征,从而可以找到测试结果,尤其是预测热故障的情况。