首页> 外文期刊>IEEE Transactions on Power Delivery >Application of MOV and gapped arresters on noneffectively grounded distribution systems
【24h】

Application of MOV and gapped arresters on noneffectively grounded distribution systems

机译:MOV和带间隙的避雷器在接地无效的配电系统上的应用

获取原文
获取原文并翻译 | 示例
           

摘要

Conditions under which the substitution of a metal-oxide varistor (MOV) arrester for a gapped silicon carbide arrester of similar rating would have been inappropriate are examined with reference to the 33 kV Staten Island system, fed from the Fresh Kills and Fox Hills Substation, in New York City. The investigation indicates that steady-state overvoltages greater than 1.73 per unit are possible on backfed systems. Saturation of transformers cannot be relied upon to decrease steady-state overvoltages even when these voltages approach 2.0 per unit. Unigrounded systems are found to have high steady-state overvoltages regardless of neutral impedance. It is demonstrated that the use of an MOV on a unigrounded system having backfeeds can result in very high arrester ratings which are costly, large, and provide greatly reduced margins. It is concluded that, under conditions of high steady-stage overvoltages during fault conditions, a gapped arrester may prove to be the best solution.
机译:参考由Fresh Kills和Fox Hills变电站供电的33 kV史坦顿岛系统,研究了用金属氧化物变阻器(MOV)避雷器替代类似等级的带间隙的碳化硅避雷器的情况,在纽约市。研究表明,在反向馈电系统上,稳态过电压可能会超过每单位1.73。即使这些电压接近每单位2.0,也不能依靠变压器的饱和来降低稳态过电压。无论接地阻抗如何,单接地系统都具有较高的稳态过电压。已经证明,在具有回馈的单接地系统上使用MOV会导致避雷器等级很高,而避雷器等级既昂贵,又大,并大大降低了裕度。可以得出结论,在故障情况下稳态电流过高的情况下,有间隙的避雷器可能是最好的解决方案。