首页> 外文期刊>IEEE Transactions on Power Delivery >Analysis of DC arc furnace operation and flicker caused by 187 Hz voltage distortion
【24h】

Analysis of DC arc furnace operation and flicker caused by 187 Hz voltage distortion

机译:187 Hz电压畸变引起的直流电弧炉运行和闪烁的分析

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

This paper analyzes an unusual flicker-like disturbance during the operation of a DC arc furnace. A harmonic resonance, excited by an excessive amount of uncharacteristic converter current harmonics, was the main cause of the disturbance. A study was performed in which the phenomenon was duplicated with the Electro-Magnetic Transients Program. The simulation model and results are described. The generation of uncharacteristic converter current harmonics under normal and abnormal converter operation are demonstrated. The significant conditions leading to the unusual 187 Hz disturbance and flicker complaints are discussed.
机译:本文分析了直流电弧炉运行过程中异常的闪烁状干扰。谐波谐振是由过多的非典型转换器电流谐波激发而引起的,是造成干扰的主要原因。进行了一项研究,其中该现象与电磁瞬态程序重复存在。描述了仿真模型和结果。演示了正常和异常转换器操作下非典型转换器电流谐波的产生。讨论了导致异常187 Hz干扰和闪烁抱怨的重要条件。