Estimation of lightning shielding failures and mid-span back-flashovers based on the performance of EHV double circuit transmission lines

机译:基于超高压双回输电线路的性能估算雷电屏蔽故障和中跨反闪

获取原文
获取原文并翻译 | 示例
           

摘要

In Japan, many unbalanced installation double-circuit EHV transmission lines were constructed to prevent simultaneous lightning faults on both the circuits. A one-line fault on the higher insulated circuit is either a shielding failure or a mid-span back-flashover. To discriminate shielding failures and mid-span back-flashovers among all the faults, the author analyzed the lightning performance of these unbalanced insulation lines. Both the unbalanced insulation lines and the balanced insulation lines are similar in the probability of causing a shielding failure and a midspan back-flashover, since both are the same in the configuration of shielding wires and phase conductors independent of the insulation mode. As a result of analysis, the author estimated that about 25/spl sim/40% of all the lightning faults on the double-circuit balanced insulation lines are shielding failures, and that few mid-span back-flashovers happen there.
机译:在日本,建造了许多不平衡安装的双回路超高压输电线路,以防止两个回路同时发生雷电故障。较高绝缘电路上的单线故障是屏蔽故障或中跨反向闪络。为了区分所有故障中的屏蔽故障和中跨反向闪络,作者分析了这些不平衡绝缘线的雷电性能。不平衡绝缘线和平衡绝缘线在引起屏蔽故障和中跨后闪络的可能性上是相似的,因为与绝缘模式无关,屏蔽线和相导体的配置相同。分析的结果是,作者估计,双回路平衡绝缘线路上所有雷电故障中约25 / spl sim / 40%是屏蔽故障,并且那里很少发生中跨反向闪络。