首页> 外文期刊>Power Delivery, IEEE Transactions on >Systematic Method to Identify an Area of Vulnerability to Voltage Sags
【24h】

Systematic Method to Identify an Area of Vulnerability to Voltage Sags

机译:识别电压暂降脆弱区域的系统方法

获取原文
获取原文并翻译 | 示例

摘要

This paper describes a systematic method for determining an area of vulnerability (AOV) to fault induced voltage sags. The concept of an AOV is very useful for evaluating vulnerability and the relationship between sensitive loads and system voltage sag performance. In general, a system performance assessment pertaining to voltage sags requires a determination of AOVs for system buses. Because voltage sags can be caused by remote faults in a transmission system, to completely identify an AOV, a large part of the power system including adjacent circuits and remote supply systems should be considered. Therefore, accurately calculating critical points and identifying AOVs are challenging tasks. In this paper, we present an effective numerical method to determine an accurate AOV in a large scale power system and to overcome limitations of other well-known methods.
机译:本文介绍了一种确定故障引起的电压骤降的脆弱区域(AOV)的系统方法。 AOV的概念对于评估脆弱性以及敏感负载与系统电压骤降性能之间的关系非常有用。通常,与电压骤降有关的系统性能评估需要确定系统总线的AOV。因为电压骤降可能是由传输系统中的远程故障引起的,所以要完全识别AOV,应考虑电力系统的大部分,包括相邻电路和远程供电系统。因此,准确计算临界点并确定AOV是具有挑战性的任务。在本文中,我们提出了一种有效的数值方法来确定大型电力系统中的准确AOV并克服其他已知方法的局限性。