首页> 外文期刊>IEEE Transactions on Power Delivery >Traveling Wave-Based Transmission Line Earth Fault Distance Protection
【24h】

Traveling Wave-Based Transmission Line Earth Fault Distance Protection

机译:行程基于波的传输线接地故障距离保护

获取原文
获取原文并翻译 | 示例
           

摘要

This paper proposes a one-terminal traveling wave (TW)-based transmission line earth fault distance protection function. It only needs the detection of the first incident modal earth fault-induced TWs, so that, the challenging detection of wavefronts reflected from the fault point is not required. Both the sampling frequency effect and inaccuracies on the wave propagation velocity are considered in order to define the distance protection zone. Simulated fault records were played back in an actual relay, allowing the comparison between a commercially existing time-domain distance protection element and the proposed one. The proposed function is more accurate and significantly reduces transmission line distance protection tripping times without dependability losses.
机译:本文提出了一个终端行驶波(TW)的传输线接地故障距离保护功能。它只需要检测第一事件模态地球故障诱导的TWS,因此,不需要挑战从故障点反射的波前的检测。考虑采样频率效应和波传播速度的不准确性,以便定义距离保护区。模拟故障记录在实际继电器中播放,允许商业上现有的时域距离保护元件和所提出的中继之间的比较。所提出的功能更准确,并且显着减少了没有可靠性损失的传输线距离保护跳闸时间。