首页> 外文期刊>IEEE Transactions on Plasma Science >Study of a circuit-breaker arc with self-generated flow. I. Energy transfer in the high-current phase
【24h】

Study of a circuit-breaker arc with self-generated flow. I. Energy transfer in the high-current phase

机译:具有自发电流的断路器电弧的研究。一,大电流阶段的能量转移

获取原文
获取原文并翻译 | 示例

摘要

This study deals with the first phase of operation, corresponding to the energy transfer between arc and gas and to the pressure rise. The experimental study is devoted to measurements of current, arc voltage, and pressure variations in N/sub 2/ and SF/sub 6/. For currents of the order of 10 kA the mean measured electric field was about 32 V/cm in SF/sub 6/ and 36 V/cm in N/sub 2/. Through a bibliographical study and a modeling approach of the interruption arc, an analysis of the role of the different mechanisms of energy transfer between the arc and SF/sub 6/ was conducted. With a 10 kA pulse, about 80% of the transfer is found to be due to convection and the rest to radiation from the arc. This transfer results in an overpressure of nearly 1 bar in SF/sub 6/ and 2 bar in N/sub 2/. It appears that the operation of this type of circuit breaker is limited to high currents: for currents below 7 kA the overpressure is lower than 0.5 bar, which does not provide efficient blowing at current zero.
机译:该研究涉及运行的第一阶段,该阶段对应于电弧和气体之间的能量传递以及压力上升。实验研究致力于测量N / sub 2 /和SF / sub 6 /中的电流,电弧电压和压力变化。对于10 kA的电流,在SF / sub 6 /中平均测得的电场约为32 V / cm,在N / sub 2 /中约为36 V / cm。通过书目研究和中断弧的建模方法,分析了弧与SF / sub 6 /之间的不同能量传递机制的作用。对于10 kA的脉冲,发现约80%的传输是由于对流引起的,其余部分是来自电弧的辐射。这种转移导致SF / sub 6 /中的压力接近1 bar,N / sub 2 /中的压力超过2 bar。似乎这种类型的断路器的操作仅限于高电流:对于低于7 kA的电流,过压低于0.5 bar,这在电流为零时无法提供有效的熔断。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号