首页> 外文期刊>Nuclear Technology >Implementation of New Cable Condition-Monitoring Technology at Oyster Creek Nuclear Generating Station
【24h】

Implementation of New Cable Condition-Monitoring Technology at Oyster Creek Nuclear Generating Station

机译:牡蛎溪核电站电缆状态监测新技术的实施

获取原文
获取原文并翻译 | 示例
           

摘要

This paper reports the results of in situ cable testing performed at the Oyster Creek Nuclear Generating Station in September 2016 to assess the aging condition of a number of cables as installed in the plant. Despite having been in service for over 40 years, our results found that these cables still met their qualification criteria, were in good working condition, and could continue to serve the plant for the foreseeable future. Some degradation in the cable insulation was noted but not as much as one would expect after more than 40 years of service in a nuclear power plant. Specifically, test results revealed that 10% of cables exhibited a noticeable degree of degradation, 30% were only slightly degraded, and the remaining 60% were essentially unaffected by aging. In the case of jacketed cables, which were assessed using walkdowns performed by the plant's personnel, almost all aging and degradation were limited to the jacket material while the underlying cable insulation was latgely unaffected. This is consistent with laboratory test results, which have shown that jacket material, especially Neoprene and Hypalon, degrade much faster than cross-linked polyethylene (XLPE) and other materials that are used for primary cable insulation.
机译:本文报告了2016年9月在Oyster Creek核发电站进行的原位电缆测试的结果,以评估工厂中安装的许多电缆的老化情况。尽管已经使用了40多年,但我们的结果发现这些电缆仍然符合其合格标准,处于良好的工作状态,并且可以在可预见的将来继续为工厂服务。注意到电缆绝缘性能有所下降,但在核电站工作超过40年后,并未达到预期的下降。具体而言,测试结果表明,10%的电缆表现出明显的降解程度,30%的电缆仅轻微降解,其余60%​​的电缆基本上不受老化的影响。对于带护套的电缆,使用工厂人员进行的停机评估,几乎所有的老化和退化都限于护套材料,而下面的电缆绝缘层则不受影响。这与实验室测试结果一致,后者表明护套材料(尤其是氯丁橡胶和Hypalon)的降解速度比交联聚乙烯(XLPE)和其他用于主电缆绝缘的材料的降解快得多。

著录项

  • 来源
    《Nuclear Technology》 |2017年第2期|93-105|共13页
  • 作者单位

    Analysis and Measurement Services Corporation, AMS 9119 Cross Park Drive, Knoxville, Tennessee 37923;

    Analysis and Measurement Services Corporation, AMS 9119 Cross Park Drive, Knoxville, Tennessee 37923;

    Analysis and Measurement Services Corporation, AMS 9119 Cross Park Drive, Knoxville, Tennessee 37923;

    Analysis and Measurement Services Corporation, AMS 9119 Cross Park Drive, Knoxville, Tennessee 37923;

    Exelon Generation Company, Oyster Creek Nuclear Generating Station, Lanoka Harbor, New Jersey 08734;

    Exelon Generation Company, Oyster Creek Nuclear Generating Station, Lanoka Harbor, New Jersey 08734;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);美国《生物学医学文摘》(MEDLINE);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Instrumentation and control; cable condition monitoring; cable-aging management;

    机译:仪表与控制;电缆状态监测;电缆老化管理;