首页> 外文期刊>Materials performance >Fouling Control of PVG Film- Type Cooling Tower Fills at Power Plants
【24h】

Fouling Control of PVG Film- Type Cooling Tower Fills at Power Plants

机译:电厂PVG薄膜型冷却塔填料的结垢控制。

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

1. CW pipelines are being damaged from corrosion caused microbiological species and the corrosiveness of the water. 2. Cooling tower fill fouling occurs mainly from suspended matter in the air, which sticks to the lower portion of the fills; micro-organisms then create a biofilm that enhances the clogging of the fills. 3. Corrosion products from the CW system are deposited along with dirt/bacteria in the cooling tower fills. 4. With the increase in fouling of cooling tower fills, the increase in local temperatures leads to precipitation of CaCO_3 on top of the foulants.
机译:1. CW管道由于腐蚀引起的微生物种类和水的腐蚀性而受到损坏。 2.冷却塔填料结垢主要是由于空气中的悬浮物粘在填料的下部造成的;然后,微生物会形成生物膜,以增强填充物的堵塞。 3.来自CW系统的腐蚀产物与灰尘/细菌一起沉积在冷却塔填料中。 4.随着冷却塔填料结垢的增加,局部温度的升高导致CaCO_3沉淀在结垢物上。