首页> 外文期刊>Journal of testing and evaluation >A Strategy to Determine Partial Discharge in XLPE Power Cables Using Acoustic Emission Detection Technique
【24h】

A Strategy to Determine Partial Discharge in XLPE Power Cables Using Acoustic Emission Detection Technique

机译:利用声发射检测技术确定XLPE电力电缆局部放电的策略

获取原文
获取原文并翻译 | 示例
       

摘要

Acoustic emission (AE) is a nondestructive technique that has unique potential for evaluating degradation and possibly for failure prediction, as well, of cross-linked polyethylene (XLPE) cables. This technique is more suited in high-voltage tests because of its external antielectromagnetism interference. The authors have demonstrated its capability toward failure prediction on XLPE cables. In this study, five sets of fifty identical XLPE cables were taken up for the investigation. These tests were carried out on both damaged and undamaged conditions. The AE data acquired during loading cycles is analyzed, and a lucid empirical relation is developed to predict their failure performance. Even though there is no pinpoint method spelled out in the open literature for the failure prediction of XLPE cables, one could appreciate the approach that impending failure is significant even at 50-60 % of maximum expected operating voltage with a reasonable error margin. Moreover, this methodology can also be applied to predict in real time the failure of similar XLPE cables made of other material systems.
机译:声发射(AE)是一种非破坏性技术,具有独特的潜力,可用于评估交联聚乙烯(XLPE)电缆的退化以及可能的故障预测。由于它的外部抗电磁干扰,该技术更适合于高压测试。作者已经证明了其对XLPE电缆进行故障预测的能力。在这项研究中,采用了五套相同的五十根XLPE电缆进行调查。这些测试是在损坏和未损坏的条件下进行的。分析了在加载周期中获取的AE数据,并建立了清晰的经验关系以预测其失效性能。即使在公开文献中没有针对XLPE电缆进行故障预测的精确方法,也可以理解这种方法,即使在最大预期工作电压的50%至60%的情况下,具有合理的误差裕度,也将导致重大故障。此外,该方法还可以用于实时预测由其他材料系统制成的类似XLPE电缆的故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号