首页> 外文期刊>Journal of Enhanced Heat Transfer >Local Flow and Heat Transfer of a 2-row Offset Strip Fin-tube Heat Exchanger
【24h】

Local Flow and Heat Transfer of a 2-row Offset Strip Fin-tube Heat Exchanger

机译:2行偏置带状翅片管热交换器的局部流动和传热

获取原文
获取原文并翻译 | 示例
       

摘要

A numerical study has been performed of the local flow and heat transfer characteristics of a 2-row offset strip fin-tube heat exchagner of 7 mm in tube diameter, with a view to investigating the mechanism of heat transfer in the heat exchanger. The increases in dimensionless local heat flux at the leading edge of he slit and the bottom surface of the fin has been examined quantitatively in the present study. It has been found that the air temeprature downstream the 2nd row of the offset strip fin-tube heat exchawger is more uniform than that of a plain plate fin-tube heat exchanger because of the augmented energy mixing effect caused by the slit. It has also found that, as the inlet air velocity is raised, the regional contribution to heat transfer decreases in the lst row and increases in the 2nd row.
机译:为了研究热交换器中的传热机理,已经对管径为7mm的2行偏置带状翅片管换热器的局部流动和传热特性进行了数值研究。在本研究中已定量检查了狭缝的前缘和鳍片底面处无量纲局部热通量的增加。已经发现,由于狭缝引起的能量混合效果的增强,偏置条形翅片管热交换器的第二排下游的空气温度比平板翅片管热交换器的空气温度更加均匀。还发现,随着进气速度的增加,区域对热传递的贡献在第一行中减小而在第二行中增大。