PRESSURE DROP IN R-245FA CONDENSATION IN TUBES FITTED WITH COILED-WIRE INSERTS

机译:R-245FA冷凝器在装有钢丝插入件的管中的压降

获取原文
获取原文并翻译 | 示例
       

摘要

This study examines pressure drop during condensation of R-245fa pure vapor inside two separate horizontal coaxial double-pipe test sections with coiled-wire inserts assembled in series. For each inserted tube and the plain tube, data were collected for mass fluxes in the range of 100 to 250 kg/m(2)s in increments of 50 kg/m(2)s for vapor qualities ranging from 0.1 to 0.9. It was observed that the pressure drop inside a horizontal tube is a complex function of vapor quality, mass velocity, and coil pitch, and in a low vapor quality region. The highest pressure drop ratio was 13.33 for a coil pitch of 3.0 mm at a refrigerant mass flux of 150 kg/m(2)s.
机译:这项研究研究了在两个单独的水平同轴双管测试段中,R-245fa纯蒸气在串联的螺旋线插入件内冷凝时的压降。对于每个插入管和普通管,收集的质量通量数据在100到250 kg / m(2)s的范围内,以50 kg / m(2)s的增量递增,蒸汽质量在0.1到0.9的范围内。可以看出,水平管内部的压降是蒸汽质量,质量速度和线圈螺距以及低蒸汽质量区域的复杂函数。在150 kg / m(2)s的制冷剂质量通量下,线圈节距为3.0 mm时,最高压降比为13.33。