Arc flash on distribution circuits is a safety issue that can impact work practices for line and substation workers. This paper shows test results for arc flash events in medium-voltage switchgear cubicles and live-front transformer enclosures. Both scenarios can result in more incident energy than the prediction of the IEEE 1584-2002. Much higher than expected energies were measured from rack-in style switchgear breaker cubicles due to the orientation of the electrodes. Live-front transformer cubicles showed wide variability that was not directly related to the enclosure size or arc directionality. Unexpectedly high energies were measured in multiple configurations. For selection of the appropriate clothing systems, incident energy multipliers are suggested based on the IEEE 1584-2002.
机译:配电线路上的电弧闪光是一个安全问题,可能会影响线路和变电站工作人员的工作习惯。本文显示了中压开关柜和带电变压器外壳中电弧闪光事件的测试结果。与IEEE 1584-2002的预测相比,这两种情况都可能导致更多的入射能量。由于电极的方向,从机架式开关柜柜中测得的能量远高于预期。带电前端变压器柜显示出很大的可变性,与外壳尺寸或电弧方向性没有直接关系。意外地,以多种配置测量了高能量。为了选择合适的服装系统,建议基于IEEE 1584-2002的入射能量倍增器。