Application of STATCOM to an Industrial Distribution System Connected to a Weak Utility System

机译:STATCOM在连接到弱电系统的工业配电系统中的应用

获取原文
获取原文并翻译 | 示例
       

摘要

The application of STATCOM or STATCON is common in transmission systems—the device has a capability of P-Q control in four quadrants. DSTATCOM (for distribution systems) and dynamic voltage regulator are somewhat synonymous. This paper describes a unique distribution system with three in-plant generators and an interconnection to a weak utility system at 44 kV; the three-phase short-circuit level at the utility source is only 151.7 MVA. So long as the generators are in operation, the power factor at the utility interconnection can be maintained close to unity and the voltage profiles in the system are acceptable—a total of 64 MW of load is served from 3–13.8-kV interconnected bus system. To control the voltage dips on loss of generation, 31 Mvar of capacitor filters (as the distribution system has considerable drive system loads and harmonic analysis study is conducted) are installed, yet the voltage dip can exceed 25%. A STATCOM can restore the voltage in one-half cycle. The STATCOM is also briefly compared with other technologies like TCR and TSC.
机译:STATCOM或STATCON在传输系统中的应用很普遍-该设备具有在四个象限中进行P-Q控制的能力。 DSTATCOM(用于配电系统)和动态电压调节器在某种程度上是同义词。本文介绍了一个独特的配电系统,该系统具有三个厂内发电机,并与44 kV弱电系统互连。市电的三相短路水平仅为151.7 MVA。只要发电​​机处于运行状态,公用事业互连处的功率因数就可以保持接近统一,并且系统中的电压曲线是可接受的-3–13.8 kV互连总线系统可为总共64 MW的负载供电。为了控制由于发电损耗而产生的电压骤降,安装了31 Mvar的电容器滤波器(因为配电系统具有相当大的驱动系统负载,并且已进行了谐波分析研究),但电压骤降可能超过25%。 STATCOM可以在半个周期内恢复电压。还简要介绍了STATCOM与TCR和TSC等其他技术的比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号