Impact of Shunt Active Harmonic Filter on Harmonic Current Distortion of Voltage Source Inverter-Fed Drives

机译:并联有源谐波滤波器对电压源逆变器馈电驱动器谐波电流失真的影响

获取原文
获取原文并翻译 | 示例
           

摘要

When applying an active harmonic filter (AHF) to mitigate the harmonic currents of voltage source inverter-fed drives (VSI), the required capacity of the AHF is generally determined by the measured harmonic current of the drives. However, when the AHF is connected to an electrical power distribution system, the total harmonic current distortion of the load actually increases owing to the change in the rectifier commutation behavior. Therefore, a higher AHF output capacity is needed to meet the expected filtering requirement. This paper investigates the impact of the AHF on the changes of the harmonic current distortion of the VSI. For this purpose, correlation analysis models are constructed, and case studies are presented to illustrate the effect with different system short-circuit levels, load conditions, and ac chokes of the VSI. Furthermore, several actual field measurement results are presented for verification. On the basis of the measured and calculated results, a margin factor is recommended for use when determining the capacity of the AHF.
机译:当应用有源谐波滤波器(AHF)来减轻电压源逆变器馈电驱动器(VSI)的谐波电流时,AHF所需的容量通常由测量的驱动器谐波电流确定。但是,当AHF连接到配电系统时,由于整流器换向行为的变化,负载的总谐波电流失真实际上会增加。因此,需要更高的AHF输出容量才能满足预期的滤波要求。本文研究了AHF对VSI谐波电流失真变化的影响。为此,构建了相关分析模型,并提供了案例研究来说明不同系统短路水平,负载条件和VSI交流电抗器的影响。此外,还提供了一些实际的现场测量结果以供验证。根据测量和计算的结果,建议在确定AHF容量时使用裕度因子。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号