首页> 外文期刊>Fuel >An integrated multi-channel electrostatic sensing and digital imaging system for the on-line measurement of biomass-coal particles in fuel injection pipelines
【24h】

An integrated multi-channel electrostatic sensing and digital imaging system for the on-line measurement of biomass-coal particles in fuel injection pipelines

机译:集成的多通道静电感应和数字成像系统,用于在线测量燃油喷射管道中的生物质煤颗粒

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

The measurement of key parameters of biomass-coal particles in a pneumatic conveying pipeline at a power plant presents a significant challenge due to the inherent complexity of the dilute particle flow and differences in physical properties between the different kinds of fuels. This paper presents the latest development in on-line continuous measurement of mean particle velocity, concentration and particle size distribution of pulverised fuel using multi-channel electrostatic sensing and digital imaging techniques. An integrated instrumentation system has been implemented to achieve the intended measurement of pulverised fuel particles. Comprehensive tests were conducted on a 150 mm bore horizontal pipe section of a large scale test facility using pulverised coal and biomass-coal blends. The results suggest that the characteristics of the pulverized fuel flow depend on the flow velocity and biomass proportion in the mixture and, to a large extent, on the biomass properties. It is found that coal particles travel faster and carry more electrostatic charge than biomass-coal blends. As more biomass particles (up to 20% by weight) are added to the flow, the particle velocity reduces, the electrostatic charge level decreases, and the flow becomes less stable in comparison with coal flow. (C) 2014 Elsevier Ltd. All rights reserved.
机译:由于稀颗粒流的固有复杂性以及不同种类燃料之间的物理特性差异,在发电厂的气力输送管道中对生物质煤颗粒的关键参数进行测量提出了重大挑战。本文介绍了使用多通道静电感应和数字成像技术在线连续测量粉状燃料的平均颗粒速度,浓度和粒径分布的最新进展。已经实施了集成的仪器系统以实现粉状燃料颗粒的预期测量。使用粉煤和生物质煤混合物在大型测试设施的150毫米孔径水平管段上进行了全面测试。结果表明,粉状燃料流的特性取决于混合物中的流速和生物质比例,并且在很大程度上取决于生物质的性质。发现与生物质-煤混合物相比,煤颗粒运动更快并带有更多的静电荷。与流中相比,随着将更多的生物质颗粒(按重量计最多占20%)添加到流中,颗粒速度降低,静电荷水平降低,并且流变得不稳定。 (C)2014 Elsevier Ltd.保留所有权利。

著录项

  • 来源
    《Fuel》 |2015年第1期|2-10|共9页
  • 作者单位

    North China Elect Power Univ, Sch Control & Comp Engn, Beijing 102206, Peoples R China;

    Univ Kent, Sch Engn & Digital Arts, Kent CT2 7NT, Kent, England;

    North China Elect Power Univ, Sch Control & Comp Engn, Beijing 102206, Peoples R China|Univ Kent, Sch Engn & Digital Arts, Kent CT2 7NT, Kent, England;

    Univ Kent, Sch Engn & Digital Arts, Kent CT2 7NT, Kent, England;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Flow measurement; Pulverised fuel; Electrostatic sensor; Digital imaging; Particle size distribution;