摘要

Armored cable has been used in building wiring systems since the early 1900s and remains an accepted wiring method today. The original product developed in the early 1900s and that which is commercially available today have significant differences in construction and performance. Likewise the demand and expectation of building wiring systems has changed. This paper explores some of those differences as well as concerns and hazards presented by the continued use of older constructions of armored cable. Testing was performed on samples of aged cables removed from service to determine impedance and temperature rise of the armor when conducting AC current. The results were compared to the DC resistance of the armor as well as the applicable Underwriters Laboratories standard. The performance of cable samples was also tested in construction configurations likely to be encountered in buildings. Results indicate that ground fault currents conducted via the armor of older cable constructions can result in fire and shock hazards where the impedance and circuit characteristics limit the fault current to below the trip level of the circuit overcurrent protective device. Temperature rise of the armor can easily exceed the rating of the conductor insulation contained therein and in some cases present a fire hazard to combustible material in contact with the cable.
机译:自1900年代初以来,铠装电缆已用于建筑布线系统中,并且至今仍是公认的布线方法。最初的产品开发于1900年代初,而如今可商购获得的产品在结构和性能上都存在重大差异。同样,建筑布线系统的需求和期望也发生了变化。本文探讨了继续使用较旧的铠装电缆结构带来的一些差异以及关注和危害。测试是从停运的老化电缆样本上进行的,以确定传导交流电流时铠装的阻抗和温度上升。将结果与装甲的直流电阻以及适用的Underwriters Laboratories标准进行了比较。电缆样本的性能也在建筑物中可能遇到的构造配置中进行了测试。结果表明,通过旧电缆结构的铠装层传导的接地故障电流会导致火灾和电击危险,其中阻抗和电路特性会将故障电流限制在电路过电流保护装置的跳闸水平以下。铠装的温度升高很容易超过其中包含的导体绝缘的额定值,在某些情况下,与电缆接触的可燃材料会引起火灾隐患。

著录项

  • 来源
    《Fire Technology》 |2011年第1期|p.107-147|共41页
  • 作者

    John E. Sleights;

  • 作者单位

    Travelers Engineering Laboratory, 90 Lamberton Road,Windsor, CT 06095, USA;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    armored cable; aging wiring system; impedance; insulation; fire;

    机译:铠装电缆;老化的布线系统;阻抗;绝缘;火;
  • 入库时间 2022-08-18 00:13:02

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号