Simple tools for the design application of smoke detectors in commercial spaces with high ceilings and/or complex geometries do not exist due to the complexity in accurately estimating smoke densities and smoke detector activation characteristics. The response of commercial smoke detectors to UL/ULC standard flaming acceptance test fires and non-standard test fires in large open spaces with ceiling heights varying from 3 m to 21 m with radial distances from the fires up to 11.4 m is measured. Two algebraic models intended for unconfined ceilings, the two-zone computer model CFAST and the computational fluid dynamics computer model FDS are compared against each other and the experimental results. The ability to predict obscuration levels and detection times for these fires is evaluated. Recommendations are made for using the various models in commercial applications.
机译:由于在准确估算烟雾密度和烟雾探测器激活特性方面的复杂性,因此在高天花板和/或复杂几何形状的商业空间中,烟雾探测器的设计应用没有简单的工具。在天花板高度从3 m到21 m且径向距离不超过11​​.4 m的大型开放空间中,测量商用烟雾探测器对UL / ULC标准燃烧可接受测试火灾和非标准测试火灾的响应。比较了用于无边天花板的两个代数模型,两区计算机模型CFAST和计算流体力学计算机模型FDS,并进行了比较。评估了预测这些火灾的遮蔽水平和检测时间的能力。建议在商业应用中使用各种模型。