首页> 外文期刊>Fire and materials >Carbon Dioxide Generation Calorimetry-errors Induced By The Simplifying Assumptions In The Standard Test Methods
【24h】

Carbon Dioxide Generation Calorimetry-errors Induced By The Simplifying Assumptions In The Standard Test Methods

机译:在标准测试方法中简化假设引起的二氧化碳生成量热误差

获取原文
获取原文并翻译 | 示例
           

摘要

Carbon dioxide generation (CDG) calorimetry is commonly used for measuring heat release rates of materials. Calorimetric equation provided in the ASTM E 2058 and the NFPA code 287 is a simplified equation since the water content in the ambient air and the fumes as well as the expansion factor of the combustion gases are neglected. This paper provides general equation for CDG calorimetry based on the Tewarson formulation. A comparison is proposed between the Standard test methods (simplified equation) and the general one. It is shown that the errors induced by the simplifying assumptions are negligible for oxygen depletion factor values commonly encountered in the Fire Propagation Apparatus (where large dilution factors of the combustion gases are used before the measurements of species concentrations).
机译:二氧化碳生成(CDG)量热法通常用于测量材料的放热率。 ASTM E 2058和NFPA代码287中提供的色度方程式是简化的方程式,因为忽略了周围空气和烟气中的水含量以及燃烧气体的膨胀系数。本文提供了基于Tewarson公式的CDG量热法的一般公式。建议在标准测试方法(简化的方程式)和通用测试方法之间进行比较。结果表明,由简化假设引起的误差对于火灾蔓延设备(在测量物种浓度之前使用较大的燃烧气体稀释因子)中通常遇到的耗氧因子值可以忽略不计。