首页> 外文期刊>Fire and materials >Cable tray fire tests in a confined and mechanically ventilated facility
【24h】

Cable tray fire tests in a confined and mechanically ventilated facility

机译:在密闭和机械通风的设施中进行电缆桥架着火测试

获取原文
获取原文并翻译 | 示例
       

摘要

Cable fires are one of the main fire hazards in nuclear power plants. As part of the cable fire spreading (CFS) campaign of the OECD PRISME-2 programme, 3 real-scale cable tray fire tests were performed in open atmosphere (1 CFS support test, named CFSS-2) and in a confined and mechanically ventilated facility (2 CFS tests, named CFS-3 and CFS-4). This study aims at investigating the effects of confined and ventilated conditions on cable tray fires that used a halogen-free flame retardant cable-type. The CFS-3 and CFS-4 tests involved 2 ventilation renewal rates of 4 and 15 h(-1), respectively. The confined conditions lead to decrease the fire growth rate and the peaks of mass loss rate and heat release rate, compared with open atmosphere. The reductions are larger for the lower ventilation renewal rate. Furthermore, it is shown that the CFS-4 test may be classified as a well-ventilated fire and the CFS-3 test as an under-ventilated fire. For this last one, its fire characteristics and its consequences in the fire room highlight an oscillatory behaviour, with the same low frequency, for about 30 minutes. These oscillations arise from successive combustions of unburnt gases.
机译:电缆火灾是核电厂的主要火灾隐患之一。作为OECD PRISME-2计划的电缆火势蔓延(CFS)活动的一部分,在露天环境中进行了3次真实规模的电缆桥架着火测试(1次CFS支撑测试,命名为CFSS-2),并在密闭且机械通风的环境中进行。工具(2个CFS测试,分别称为CFS-3和CFS-4)。这项研究旨在调查密闭和通风条件对使用无卤阻燃电缆类型的电缆桥架火灾的影响。 CFS-3和CFS-4测试分别涉及2次通气更新率,分别为4和15 h(-1)。与露天环境相比,狭窄的条件导致着火率降低,质量损失率和放热率的峰值降低。对于较低的通风换新率,减少量更大。此外,已表明CFS-4测试可归类为通风良好的火灾,CFS-3测试可归类为通风不足的火灾。对于这最后一个,它的着火特性及其在火室中的后果突出了大约30分钟的振荡行为,并且具有相同的低频。这些振荡是由未燃烧气体的连续燃烧引起的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号