首页> 外文期刊>Experimental Heat Transfer >Condensation heat transfer and pressure drop characteristics of R-134a inside the flattened tubes at high mass flux and different saturation temperature
【24h】

Condensation heat transfer and pressure drop characteristics of R-134a inside the flattened tubes at high mass flux and different saturation temperature

机译:高质量通量下扁平管内扁平管内R-134a的凝结传热和压降特性及不同饱和温度

获取原文
获取原文并翻译 | 示例
       

摘要

In this study, heat transfer coefficients and pressure drops of R-134a inside round and flat tubes are investigated experimentally with mass flux of 450, 550, and 650 kg m(-2) s(-1) at saturation temperatures of 35 degrees, 40 degrees, and 45 degrees C. The effects of mass flux and saturation temperature on heat transfer coefficient and pressure drop are examined. The maximum enhancement factor and pressure drop penalty are obtained by flat tube (FT-2) up to 2.101 at 450 kg m(-2) s(-1) and 3.01 at 650 kg m(-2) s(-1), respectively. The correlation for flat tubes is proposed to predict the heat transfer coefficient within +/- 20% error.
机译:在该研究中,通过450,550和650kg m(-2)S(-1)的质量通量在实验上实验研究R-134a内部和扁平管内的传热系数和压降,在35度的饱和温度下, 40度和45℃。检查质量磁通量和饱和温度对传热系数和压降的影响。最大增强因子和压降损失是通过扁平管(FT-2)在450kg m(-2)S(-1)和3.01处的扁平管(FT-2)获得,在650kg m(-2)s(-2),分别。提出了扁平管的相关性以预测+/- 20%误差内的传热系数。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号