首页> 外文期刊>Environmental Engineering Science >Lead Release to Drinking Water from Galvanized Steel Pipe Coatings
【24h】

Lead Release to Drinking Water from Galvanized Steel Pipe Coatings

机译:从镀锌钢管涂层饮用水铅释放

获取原文
获取原文并翻译 | 示例
       

摘要

Problems identified with elevated lead in drinking water associated with galvanized steel pipes were recently hypothesized to result from lead accumulation on galvanized steel pipe surfaces from upstream lead service pipes. However, historical research documents that the grade of zinc typically used for galvanizing contains a minimum of 0.5% lead and can itself be a significant long-term source of lead, which may explain some recent lead contamination problems associated with galvanized steel. Surface analysis of various galvanized steel pipes and fittings installed from 1950 to 2008 demonstrated that the concentration of lead in the original zinc coating can range from nondetect to nearly 2%, dependent on the manufacturer and fitting type. Since cadmium is also present in many zinc coatings, but not in lead pipe, leaded solder, or brass, correlation of zinc concentration to both lead and cadmium concentrations in water was considered as a possible fingerprint implicating the coating on galvanized steel as a lead source; bench-scale tests of metal leaching from harvested galvanized steel pipes were used to validate this approach. Using profile sampling, individual homes with galvanized steel pipes as a primary lead source were identified in Washington, DC, Providence, RI, Chicago, IL, and a city in Florida. In some cases, the levels of lead from this source were very significant (100 mu g/L) and can be exacerbated by installation of a copper pipe upstream during partial service line replacements.
机译:最近假设用镀锌钢管相关的饮用水升高的铅铅鉴定出问题,从镀锌钢管表面上的铅积聚从上游铅服务管道产生。然而,历史研究文件,即通常用于镀锌的锌等级含有至少0.5%的铅,并且本身可以是一个重要的长期铅来源,其可以解释与镀锌钢相关的一些近期铅污染问题。从1950年到2008年安装的各种镀锌钢管和配件的表面分析表明,原始锌涂层中铅的浓度可从非特征到近2%,取决于制造商和配件类型。由于镉也存在于许多锌涂层中,但不在铅管中,铅焊料或黄铜,锌浓度与水中铅和镉浓度的相关性被认为是可能的指纹,将镀锌钢涂布为铅源。 ;采用从收获的镀锌钢管浸出的金属浸出的长凳尺度试验来验证这种方法。使用简介采样,在华盛顿特区,直流,普罗维登斯,ri,芝加哥,il和佛罗里达州的一个城市中鉴定了作为主要铅来源的个别房屋。在某些情况下,来自该来源的铅水平非常显着(>100μg/ L),并且可以通过在部分服务线替换期间安装上游的铜管来加剧。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号