首页> 外文期刊>Engineering Structures >Experimental study on failure modes and retrofitting method of latticed transmission tower
【24h】

Experimental study on failure modes and retrofitting method of latticed transmission tower

机译:格式透射塔故障模式及改造方法的试验研究

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Recent years have witnessed an increasing number of transmission towers collapsing under strong winds. Therefore, a retrofitting technique on diagonal bracings is proposed in this paper to enhance the load-carrying capacity of existing transmission towers based on a thorough exploration of the failure mechanism of transmission towers in working conditions. A pair of double-panel subassemblages of a transmission tower with one's diagonal members retrofitted and the other not were statically tested to study the failure modes and to evaluate the retrofitting effects. The experimental results reveal that in the original tower subassemblages the diagonal members are vulnerable to buckling, which could lead to structural failure, while in the retrofitted specimen the most vulnerable member is the leg member rather than the diagonal bracings, which is accompanied by a change of the failure mode of the subassemblage. The ultimate lateral and vertical loads applied on the retrofitted subassemblage increase significantly compared with the original subassemblage.
机译:近年来,目睹了在强风中坍塌的越来越多的传动塔。因此,在本文中提出了一种对对角支护的改造技术,以提高现有传动塔的承载能力,基于在工作条件下的传动塔故障机构的彻底探索。一对带有一个人对角线构件的传输塔的双面板子组件,并在另一个没有静态测试以研究故障模式并评估改装效果。实验结果表明,在原始塔子组件中,对角线构件容易弯曲,这可能导致结构故障,而在改装样品中,最脆弱的构件是腿部构件而不是对角线支撑,伴随着变化子组件的失败模式。与原始子组件相比,应用于改装子组件上的最终横向和垂直载荷增加。

著录项

  • 来源
    《Engineering Structures》 |2021年第1期|111365.1-111365.14|共14页
  • 作者

    Xie Qiang; Zhang Jian;

  • 作者单位

    Tongji Univ Coll Civil Engn Siping Rd 1239 Shanghai 200092 Peoples R China|Tongji Univ Key Lab Performance Evolut & Control Engn Struct Minist Educ PRC Shanghai Peoples R China;

    Tongji Univ Coll Civil Engn Siping Rd 1239 Shanghai 200092 Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Transmission tower; Subassemblage test; Failure mode; Ultimate capacity; Tower retrofitting;

    机译:传输塔;子组件测试;故障模式;极限容量;塔改装;