BAS COMPUTER TRENDING CHILLED WATER USAGE IN DOLLARS: The BAS computer shall collect pertinent electrical (energy, kWh, kW) consumption from electrical power panel EPFNL-1 and BAS control and metering devices to determine operating cost. Those components providing input to the software program are: 1. Electrical energy for air conditioning during the cooling season via electrical meter EM-1; 2. Outdoor air temperature (drybulb and wetbulb) via OATT (outdoor air temperature [enthalpy]); 3. Chilled water supply temperature transmitter via CHW-STT (chilled water supply temperature); 4. Chilled water return temperature transmitter via CHWRTT (chilled water return temperature); 5. Chilled water in gpm via CHWM (chilled water flow); and 6. Cost of energy at $0.09/kWh.
机译:BAS计算机以美元为单位出售冷水的使用:BAS计算机应从配电盘EPFNL-1和BAS控制和计量装置收集有关的电(能量,千瓦时,千瓦)能耗,以确定运行成本。提供软件程序输入的那些组件是:1.冷却季节中通过电表EM-1的空调用电能; 2.通过OATT的室外空气温度(干球和湿球)(室外空气温度[焓]); 3.通过CHW-STT(冷水供应温度)的冷水供应温度变送器; 4.通过CHWRTT(冷水回水温度)的冷水回水温度变送器; 5.通过CHWM(冷水流量)以gpm为单位的冷水; 6.能源成本为$ 0.09 / kWh。