DURING the summer and fall of 1931, measurements at the Harris J. Ryan Laboratory, Stanford University, Calif., extended the range of corona loss data for conductor sizes beyond those investigated during 1930. In these latter tests the 3 conductor specimens studied were a 1.125-in. hollow copper cable, a 1.49-in. hollow copper cable, and a 2.0-in. hollow aluminum cable. The losses were measured on a 3-phase line 700 ft. long. Voltages as high as 600 kv. between lines were used.
机译:在1931年夏季和秋季,加利福尼亚州斯坦福大学的Harris J. Ryan实验室进行的测量将电晕损耗数据的范围扩大到1930年期间调查的范围之外。在这些后期测试中,所研究的3个导体样本均为1.125英寸空心铜电缆,1.49英寸。中空铜缆和2.0英寸空心铝电缆。损耗是在700英尺长的三相线上测量的。电压高达600 kv。使用线之间。