摘要

There are several changes in the 2002 national Electrical Code that are worthy of review. The first, in Article 110, Requirements for Electrical Installations, will be encountered mainly in switchboard rooms in other than dwelling occupancies. This is an entirely new requirement: "110.16 Flash Protection. Switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing or maintenance while energized shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing or maintenance of the equipment.
机译:2002年国家电气规范中有几项更改值得回顾。第一条,在第110条,《电气安装要求》中,将主要在住宅以外的配电室中遇到。这是一个全新的要求:“ 110.16闪存保护。在非住宅居住的配电盘,配电盘,工业控制面板和电动机控制中心,通电时可能需要检查,调整,维修或维护,应在现场标记为警告合格人员,防止潜在的电弧危险标记的位置应使合格人员在检查,调整,保养或维修设备之前可以清楚看到。