During a recent National Electrical Code (NEC) training program, inquiries about ground-fault protection of equipment (GFPE) were raised. Two questions were: Why is ground-fault protection required for large equipment rated at 1,000 volts (V) or less, and what are the requirements for GFPE when the equipment is installed in healthcare distribution systems? The third question related to required performance testing for installed GFPE. This article addresses each of these questions. First, let's look at the reason GFPE is required. It protects large equipment from devastating arcing events and destructive burn-downs. If a phase-to-ground voltage is 120V, GFPE is generally not an NEC requirement. In a circuit of 277V to ground, electric arcs generate significant amounts of heat and an arcing fault is readily sustained.
机译:在最近的美国国家电气法规(NEC)培训计划中,提出了有关设备接地故障保护(GFPE)的询问。有两个问题:为什么额定功率为1,000伏(V)或更低的大型设备需要接地故障保护?当设备安装在医疗保健配电系统中时,对GFPE的要求是什么?第三个问题与已安装的GFPE所需的性能测试有关。本文解决了每个问题。首先,让我们看一下需要GFPE的原因。它可以防止大型设备遭受毁灭性的​​电弧事件和破坏性的烧毁。如果相接地电压为120V,则GFPE通常不是NEC要求。在接地电压为277V的电路中,电弧会产生大量热量,并且电弧故障很容易持续。