首页> 外文期刊>Electrical contractor >Sizing Conductors, Part (ⅩⅩⅩⅣ)
【24h】

Sizing Conductors, Part (ⅩⅩⅩⅣ)

机译:上浆导体,第ⅩⅩⅩ部分

获取原文
获取原文并翻译 | 示例
           

摘要

Article 240, in the national electrical code (NEC), provides general requirements for overcurrent protection and overcurrent protective devices. Also covered in Article 240 are overcurrent protection requirements for supervised industrial installations operating at voltages of not more than 1,000 volts (V), nominal. Section 240.4(E) contains a list of sections where requirements for tap conductors are located. The most referenced section in 240.4(E) is probably 240.21. In accordance with 240.2, overcurrent protection shall be provided in each ungrounded circuit conductor and shall be located at the point where the conductors receive their supply except as specified in 240.21(A) through (H). While branch circuits, services, busways, motors, generators and batteries. While this section mentions branch circuits, most of the rules are for feeder taps and transformer secondary conductors.
机译:国家电气法规(NEC)中的第240条规定了过电流保护和过电流保护装置的一般要求。第240条还涵盖了在额定电压不超过1,000伏(V)的情况下进行监督的工业设施的过电流保护要求。第240.4(E)节包含分接头导体要求所在的节列表。 240.4(E)中引用最多的部分可能是240.21。根据240.2的规定,每条未接地的电路导体均应提供过电流保护,并且应位于导体接受供电的位置,除非240.21(A)至(H)规定。同时分支电路,服务,母线槽,电动机,发电机和电池。尽管本节提到分支电路,但大多数规则是针对馈线抽头和变压器次级导体的。